Select your language

Vortex FP

Manufacturer: Crowcon
Vortex FP Enclosure Certification Certificate
Vortex FP Datasheet
Vortex FP Manual (Iss 3 – Jan 15)

Designed for when resilience matters most, the Vortex FP and Vortex FP Compact are ATEX certified Exd Flameproof gas detector control panels, ideal for use in hazardous areas such as on offshore production platforms or refineries. Alongside all of the standard Vortex features, Vortex FPs come with a display that allows interrogation without opening the system enclosure, for enhanced durability.

Ideal for use in Zone 1 or Zone 2 hazardous areas, the Vortex FP and FP Compact are fireproof and highly durable, with a display fitted with magnetic switches which enables the system to be interrogated or inhibited without opening the system enclosure. Available in two sizes, there is a Vortex FP suitable for any space, however restrictive.

All day-to-day operations can be completed via push buttons on the front panel, removing the requirement for hit-work permits to complete everyday tasks. Instant indication of system status is provided by the fault and alarm LEDs on the front panel, with all relays monitored continuously.

Using Vortex PC software, customisation is easy and user-friendly, plus it uses industry standard Modbus RTU communication links, with an option to modify this to Profibus, making it compatible with a variety of control systems.

  • Available in 2 sizes
  • Vortex PC software
  • ATEX certified
  • Water and dust resistant to IP66
  • Continuous relay monitoring

Simple to Use

  • All day-to-day operations can be completed via push buttons on the front panel, removing the requirement for hot-work permits to complete everyday tasks
  • Fault and alarm LEDs on the front panel provide instant indication of system status
  • Alarm and channel settings can be adjusted from the front panel

Highly Flexible

  • Available in two sizes, including a compact format for use in areas where space is a limiting factor
  • Uses Vortex PC software which allows easy customisation is incredibly user-friendly
  • Uses industry standard Modbus RTU (or optionally Profibus) communications links, which is simple to integrate with PLC, DCS or SCADA control systems

Robust and Reliable

  • Water and dust resistant to IP66
  • All relays are monitored continuously ensuring full functionality and compliance at all times
  Vortex Vortex Rack/Panel
Size 440 x 640 x 332mm (17.3 x 25 x 13 ins) 450 x 330 x 289mm (17.6 x 13 x 11.4 ins)
Weight 70Kgs (154lbs) approx. 37.5kgs (83lbs) approx.
Enclosure material LM25 aluminium with polyester powder coating
Ingress protection IP66
Channels Up to 12 (1 to 3 4-way input modules)
Operating temperature -10°C to +40°C (14°F to +140°F)
Humidity 0-95% RH non-condensing
Inputs Gas    2 or 3 wire 4-20mA (sink or source), 0-5V
  Fire – smoke & heat detectors, manual call-points   Up to 3 loops, Up to 20 devices per loop
Outputs External audible/visual alarm drive Via relays, four 24Vdc 0.5A supplies provided.
Relays Type Up to 32 SPCO with bus extension module Relay limitations: 1 or 2 input modules: 2 relay modules max. (16 relays) 3 input modules: 1 relay module only (8 relays)
  Assignment – Common Battery back-up not available
  Assignment – Voting Alarms, faults and system events
  Relay modes    Energised/de-energised, latched/non-latched, time-delayed, pulsed
Digital communications DCS/PLC/PC:  RS-485 Modbus or Profibus
Local configuration link: RS-232 (configuration software and lead supplied)
Event logging Up to 300 alarm, power, fault, system events are stored in Non-Volatile Memory
Panel indication Channel number:  2-digit 7-segment Green LED
Gas reading: 4-digit 7-segment Red LED
Measurement units:  % LEL, ppm, % Vol, Fire
Power:  Green LED
Battery OK:  Green LED
Run/hold indication:  Green LED
Channel test mode:  Flashing Amber LED
System fault – integrity watchdog:  Amber LED
Displayed information can be altered and outputs can be inhibited during calibration using a magnetic key
Alarm indication Audible – internal sounder:  Piezo
Visual – Alarm: Level 1 & 2, Red LED; Fault – Per channel, Amber LED; Inhibit – Per zone, Amber LED
Power AC mains/DC: 110 or 240Vac 3.2A max 150W PSU 20 – 30Vdc 85 – 264Vac 0.8A max 75W PSU 20 – 30Vdc
  Battery back-up: not available
Approvals Low voltage directive: EN61010-1
EMC: Directive 2014/30/EU: EN50270, FCC: CRF47 Part 15, ICES-003
ATEX: Ex II 2G D Zone 1, Zone 2, IECEx optional
Functional safety Validated to IEC61508
Copyright MAXXmarketing GmbH
JoomShopping Download & Support