The Multiscan++ S2 from Sensitron is a SIL2 certified, advanced multifunctional gas detection control panel designed for maximum flexibility. Capable of monitoring up to 256 gas detectors, it also has a range of self-testing facilities to take place to detect and localise possible failures so you can be confident your site is always protected.
The Sensitron Multiscan++ S2 is a SIL2 certified, advanced multifunction gas detection control panel designed to meet the need for highly flexible systems. The system can manage and monitor up to 256 gas detectors, making it ideal for large sites with more complex requirements across a wide range of industries.
With a powerful microprocessor, the Multiscan++ S2 has a wide range of self-testing capabilities, allowing it to detect and localise possible failures with all-important rapidity.
The event log is fully viewable from the display on the unit itself, as well as having the option of PC download, for versatile information access.
With its capacity for monitoring large numbers of monitors, the Multiscan++ S2 is a versatile system, ideal for use across a wide range of applications and industries including refineries, pharmaceutical and petrochemical plants and the food and beverage industry.
- Highly flexible
- ATEX and SIL2 certified
- Up to 256 inputs
- Up to 2 closed RS485 (EIA-485) galvanic isolated loops
- Self-testing functionality
| Size | H470 x W426 x D148 mm (18.5 x 16.77 x 5.83ins) |
| Weight | Rack version: 4.5 kg Box version: 6.6 kg (without batteries) |
| Enclosure material | ABS or aluminium rack |
| Power | Box version: power supply with Vout=27.6 Vdc / Iout=4A, Vin=110 Vac or 220 Vac selectable by a manual switch. Possibility to place two 12V 7Ah batteries. Rack version: connect to an external 24Vdc power supply |
| Operating temperature | 0 / +50°C |
| Humidity | 15 / 85% RH non condensing |
| Inputs | 8 inputs 4-20 mA on board, additional inputs available via the remote modules. Sensitron gas detectors can be also connected directly on RS485 bus. The total inputs number depends on the gas panel model: Multiscan++ 256: up to 256 inputs Multiscan++ 128: up to 128 inputs Multiscan++ 64: up to 64 inputs Multiscan++ 32: up to 32 inputs |
| Outputs | Multiscan++ 256/128/64/32: 8 relays on board
Additional outputs available via the remote modules, the |
| Communication Port | Galileo or Modbus for field communication Modbus for the supervision |
| Event logging | The event log can be visualised from the gas panel or by the software |
| Panel indication | LCD display 18 status LEDs |
| Approvals | EMC, ATEX |
| Functional Safety | SIL2 |
JoomShopping Download & Support